معايرة حماية الحمل الزائد للمحركات
حددوا ال
SF أولاً
اذا كان 1.15 او يزيد فتكون ال OL
1.25 x FLA
اما اذا كان اصغر من 1.15
فتكون ال OL
1.15 x FLA
نص القاعدة كما ورد في المعيار الكندي
28-306 Rating or trip selection of overload devices (see Appendix B)
1) Overload devices responsive to motor current, if of the fixed type, shall be selected or rated or, if
of the adjustable type, shall be set to trip at not more than the following:
a) 125% of the full load current rating of a motor having a marked service factor of 1.15 or
greater; or
b) 115% of the full load current rating of a motor that does not have a marked service factor or
where the marked service factor is less than 1.15